Technical Specification of LEDs
1. LED Light Fitting 150W, Flood Light, 230V, AC:
LED Flood Light luminary, 230V, 50Hz, AC, complete with LED, charger ballast etc inbuilt. Cradle/clamp for mounting.
|
LED light technical specification
|
Wattage : 150W
System lumen : 13500
Housing : Pressure die cast Aluminum housing with corrosion resistant polyester
powder coating & safety as per IEC60598 / IS 10322.
IP protection : IP 65 as per IEC 60529.
Diffuser : Toughened glass
Power factor : >0.9
Harmonics : Should be less than 15%
Mounting : Cradle
Surge : 4KV
Colour Temp. : 5700K +/- 300K
CRI : >70
Life : Burning hours 50000
Application : Area lighting
General:
-
LED lamps of PHILIPS Lumileds/ NICHIA / OSRAM / SEOUL / Cree/ Samsung/ make shall be used for the purpose.
-
Photometric measurements in accordance with LM-79/IS: 16105/2012 & IS:16106/2012
-
The LED Module(s), Driver gear, etc. shall be designed in such a way so that temperature of heat sink shall not exceed 150 deg.C above the ambient temperature.
2. LED Light Fitting 90W, Street Light, 230V, AC:
LED Street Light luminaire, 230V, 50Hz, AC, complete with LED, charger ballast etc inbuilt.
Wattage : 90W
System lumen : 7650
Housing : Pressure die cast Aluminum housing with corrosion resistant polyester
powder coating & safety as per IEC60598 / IS 10322.
IP protection : IP 66
Power factor : >0.9
Harmonics : Should be less than 15%
Surge : 4KV
Colour Temp. : 5700K +/- 300K
CRI : >70
Application : Road lighting
Suitable : for 50-60mm OD pipe
General:
-
LED lamps of PHILIPS Lumileds/ NICHIA / OSRAM / SEOUL / Cree/ Samsung/ make shall be used for the purpose.
-
Photometric measurements in accordance with LM-79/IS: 16105/2012 & IS:16106/2012
-
The LED Module(s), Driver gear, etc. shall be designed in such a way so that temperature of heat sink shall not exceed 150 deg.C above the ambient temperature.
3. LED Light Fitting 25W, Street Light, 230V, AC:
LED Street Light luminaire, 230V, 50Hz, AC, complete with LED, charger ballast etc inbuilt.
Wattage : 25W
System lumen : 2000
Housing : Pressure die cast Aluminum housing with corrosion resistant polyester
powder coating & safety as per IEC60598 / IS 10322.
IP protection : IP 65 as per IEC 60529.
Power factor : >0.9
Harmonics : Should be less than 15%
Surge : 4KV
Colour Temp. : 5700K +/- 300K
CRI : >70
Life : Burning hours 50000
Application : Road lighting
Suitable for : 50-60mm OD pipe
General:
-
LED lamps of PHILIPS Lumileds/ NICHIA / OSRAM / SEOUL / Cree/ Samsung/ make shall be used for the purpose.
-
Photometric measurements in accordance with LM-79/IS: 16105/2012 & IS:16106/2012
-
The LED Module(s), Driver gear, etc. shall be designed in such a way so that temperature of heat sink shall not exceed 150 deg.C above the ambient temperature.
4. LED 9W BULB, 230V, AC:
LED Bulb, 230V, 50Hz, AC, Pin type.
Wattage : 9W
System lumen : ≥750
Housing : Pressure die cast Aluminum housing with corrosion resistant polyester
powder coating & safety as per IEC60598 / IS 10322.
IP protection : IP 65 as per IEC 60529.
Power factor : >0.9
Harmonics : Should be less than 15%
Surge : 4KV
Colour Temp. : 5700K +/- 300K
CRI : >70
Life : Burning hours 50000
Application : Residential lighting
Voltage Range : 120 - 270 volt.
General:
-
LED lamps of PHILIPS Lumileds/ NICHIA / OSRAM / SEOUL / Cree/ Samsung/ make shall be used for the purpose.
-
Photometric measurements in accordance with LM-79/IS: 16105/2012 & IS:16106/2012
-
The LED Module(s), Driver gear, etc. shall be designed in such a way so that temperature of heat sink shall not exceed 150 deg.C above the ambient temperature.
5. LED 8W, Tube Rod, 230V, AC:
LED Tube Rod, 230V, 50Hz, AC.
Wattage : 8-9W
System lumen : ≥520
Housing : Pressure die cast Aluminum housing with corrosion resistant polyester
powder coating & safety as per IEC60598 / IS 10322.
IP protection : IP 65 as per IEC 60529.
Power factor : >0.9
Harmonics : Should be less than 15%
Surge : 4KV
Colour Temp. : 5700K +/- 300K
CRI : >70
Life : Burning hours 50000
Application : Residential lighting
Voltage Range : 180 - 260 volt.
General:
-
LED lamps of PHILIPS Lumileds/ NICHIA / OSRAM / SEOUL / Cree/ Samsung/ make shall be used for the purpose.
-
Photometric measurements in accordance with LM-79/IS: 16105/2012 & IS:16106/2012
-
The LED Module(s), Driver gear, etc. shall be designed in such a way so that temperature of heat sink shall not exceed 150 deg.C above the ambient temperature.
6. LED Light Fitting 40W, Post Top, 230V, AC:
LED Post Top luminaire, 230V, 50Hz, AC, complete with LED, charger ballast etc inbuilt.
Wattage : 40W
System lumen : 2400
Housing : Pressure die cast Aluminum, clear acrylic reflector housing with
safety as per IEC60598 / IS 10322.
IP protection : IP 65 as per IEC 60529.
Power factor : >0.9
Harmonics : Should be less than 15%
Surge : 4KV
Colour Temp. : 5700K +/- 300K
CRI : >70
Life : Burning hours 50000
Application : Amusement Park/Path way
Voltage Range : 140 - 260 volt.
General:
-
LED lamps of PHILIPS Lumileds/ NICHIA / OSRAM / SEOUL / Cree/ Samsung/ make shall be used for the purpose.
-
Photometric measurements in accordance with LM-79/IS: 16105/2012 & IS:16106/2012
-
The LED Module(s), Driver gear, etc. shall be designed in such a way so that temperature of heat sink shall not exceed 150 deg.C above the ambient temperature.
General and applicable to all items
-
LED Street light Luminaries shall conform to IS:16107/2012 complete with electronic control gear for LED Luminaries conforming to IS:16104/2012 transparent cover made out of min. 3mm thick toughened glass duly wired for use on 120V-260 V,AC, 50Hz power supply.
-
Sealing shall be done in the design that there is no water ingress anywhere.
-
Operating Temperature Range: -10ºC to +50ºC
-
Operating Humidity: 10% to 90% RH
-
Control Gear: Prewired with PVC insulated Copper wiring up –to terminal block.
-
Usage Hours: 10 to 12 hrs per day
-
IP Protection: Luminary, Optical & Control Gear compartment with IP65 or more
-
Testing Facility: In-house testing facility for Quality Assurance should be available. Bidders must submit necessary documents to support the same.
-
Warrantee: not less than 02 years
-
Bidder has done/ executed similar works in state/central govt./PSU/500 Fortune Company not less than 30% of the estimated cost and certificate of satisfactory completion & performance from the clients to be submitted with offer.
-
Bidder is either manufacturer or authorized dealer distributor or agent. A certificate to be submitted of manufacturer in case the bidder is dealer/distributer/agent of manufacturer.
-
Tenderers shall furnish complete & satisfactory type test certificate before dispatch.
-
Data sheet of LED used along with its dimensions shall be furnished along with the tender.
-
Suppliers shall furnish proof of procurement of LEDs from the above OEMs.
-
LEDs must be mounted on MCPCB which should be made up of aluminium metal core.
-
All the components shall be properly fixed and all the soldering points shall be with good finish.
-
Lumen maintenance from NABL approved Govt lab for 2000 hrs shall be furnished with offer.
-
Payment Milestones:
a) After Supply of LED street lights /bulbs at store: 90%
b) After installation at site: 5%
c) After one year of supply: 2.5%
d) After two year of supply: 2.5%
Minimum essential plant and machinery required for LED lighting system.
a) Photometric integrator for testing lumen output and chromaticity co-ordinates of luminaire.
b) Air-conditioned dust free room for soldering of PCBs
c) SMD reflow machines for soldering SMD LEDs
d) Temperature controlled soldering iron.
e) Power analyzer
f) Oscilloscope
g) multimeter
h) Lux/lumen meter
i) Tested luminaire of the same model and design being offered shall be available with the firms for measuring total lumen output.
Note: At least one type tested sample (with lumen maintenance report for 2000 hrs or more) shall be retained with the manufacturer duly sealed by the test lab for reference during inspection. The bidder has to offer for inspection to M/S XYZ before dispatch of LED light fitting. The M/S XYZ reserves right for shop floor inspection or may give clearance of dispatch witnessing the test document.
Download PDF